Seitenansicht 0
Hydronic separator-manifold
HydroLink™
Function
The Hydrolink, a new device combining a hydronic separator and
distribution manifold, is used in heating and air-conditioning
systems to allow di
erent heat adjustments of the various rooms
when there is only one boiler or chiller.
The various
are compact, and can be easily in
any kind of hydronic circuit, with the advantages of ease of
installation and a saving of useful living space.
Patent application No. MI2001A001270
cert. n ° 0003
ISO 9001
Product range
Part # 31091 Exter nal 2+2 separator-manifold. Complete with support brackets and pre-formed insulation Size 1 1/4”; branches 1”
Part # 31092 External 3+1 separator-manifold. Complete with support brackets and pre-formed insulation Size 1 1/4”; branches 1”
Part # 31090 Built-in 2+1 separator-manifold. Complete with pre-formed insulation Size 1”; branches 1”
Technical characteristics
Body
leets detniaP :ydoB - :lairetaM
Medium: Water and non-hazardous glycol solutions
%05:elocylg fo egatnecrep xaM
)rab 6( isp 09 :erusserp gnikrow .xaM
Te )C°011÷ 0( F°032 ot 23 :egnar erutarepm
Connections: - main: 3+1 and 2+2: 1 1/4” F NPT
2+1: 1” F NPT
- branches: 3+1 and 2+2: 1” M NPT
2+1 (bottom): 1” M NPT
2+1 (side): 1” F NPT
- air vent valve: 3+1, 2+2 and 2+1: 1/2” F straight
- drain cock: 3+1, 2+2 and 2+1: 1/2” F straight
Center distances:
- main: 3+1 and 2+2: 3 1/8” (80 mm)
2+1: 2 3/8” (60 mm)
- branches: 3+1 and 2+2: 3 1/2” (90 mm)
2+1: 3 1/2” (90 mm)
Insulation
Material: Closed-cell expanded PEX
Thickness: 3/4” (20 mm)
Density: - inner part: 2 lb/ft
3
(30 kg/m
3
)
- outer part: 3 lb/ft
3
(50 kg/m
3
)
Thermal conductivity: - at 32°F (0°C): 0.26 BTU/in (.038 W/mK)
- at 100°F (40°C): 0.31 BTU/in (.045 W/mK)
Vapor resistance coe
cient (DIN 52615): > 1.300
Temperature range: 32 to 212°F (0÷100°C)
Fire resistance (DIN 4102): Class 1 (Class B2)
Flow Characteristics
Maximum recommended
rates at connections:
Branches Primary Secondary (total)
2+1 9 gpm (2.0 m
3
/h) 22 gpm (5 m
3
/h)
2+2 11 gpm (2.5 m
3
/h) 26 gpm (6 m
3
/h)
3+1 11 gpm (2.5 m
3
/h) 26 gpm (6 m
3
/h)
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - HydroLink™

Hydronic separator-manifoldHydroLink™FunctionThe Hydrolink, a new device combining a hydronic separator anddistribution manifold, is used in heat

Seite 2 - HydroLink

DimensionsACBCHILD EF GAMAACBCEHIGD FLACBCEGHFDALAAI38487Patent ApplicationNo. MI2001A 001270Series 559HydroLink™Pmax 90 psi - Tmax 230°FPatent Ap

Seite 3

Support bracketsThe HydroLink externalversions 2+2 and 3+1 aresupplied complete withsuitable wall-mountingbrackets, which make itpossible to adjust th

Seite 4 - HydroLink 3+1

0,250,50,751,01,251,51,752,02,2510080604020-2001-51--5051015208CALEFFI0,250,50,751,01,251,51,752,02,2520CALEFFICALEFFICALEFFI10086421008642CALEFFI1008